無効電力制御器の導入を考慮したタップ切替変圧器の電圧推定に関する検討

書誌事項

タイトル別名
  • Study on a Voltage Estimation of Tap Changing Transformer in Consideration of SVC Introduction
  • ムコウ デンリョク セイギョキ ノ ドウニュウ オ コウリョ シタ タップ キリカエ ヘンアツキ ノ デンアツ スイテイ ニ カンスル ケントウ

この論文をさがす

抄録

Recent years, installation of PV system is active by the environmental problem and feed in tariff system. Due to PV's output fluctuation, the Static Var Compensator (SVC) made by power electronics technology is planning to install in distribution system. The SVC is expected for maintain the voltage. But SVC differs in a theory of operation of the existing voltage controller Load Ratio control Transformer (LRT) and Step Voltage Regulator (SVR). Because the SVC operation makes the system impedance changes, the existing voltage controller may not operate effectively. In this study, the intelligent-control method which used the RBF network is proposed. This method can reduce the effects of the SVC operation by including the performance characteristics of SVC in the conventional method. An advantage of unnecessary arrangement attention of the SVC setup node and easy cooperation with the existing equipment is obtained by applying this method.