多地点同期位相計測に基づく電力系統広域安定度推定における観測地点変更時の精度向上

書誌事項

タイトル別名
  • Improvement of the Evaluation of the Wide Area Power System Stability Based on Multiple Synchronized Phasor Measurements with Observation Sites Changed
  • タチテン ドウキ イソウ ケイソク ニ モトズク デンリョク ケイトウ コウイキ アンテイド スイテイ ニ オケル カンソク チテン ヘンコウジ ノ セイド コウジョウ

この論文をさがす

抄録

This paper presents a method for monitoring the power system stability based on wide area phasor measurements. The authors have developed a method for detecting inter-area low-frequency modes from measured small oscillations associated with the load fluctuation by approximating filtered oscillations as a simplified oscillation model. The advantage of this method is that steady state phasor fluctuations are available to evaluate the stability of the power system. In this paper, another type of the filter based on the FFT analysis is developed for improving the accuracy of identified eigenvalues with observation sites changed. The method based on the FFT-based filtering is also applied to extract low-frequency oscillations from phasor data of one observation site. Some numerical analyses demonstrate the effectiveness of the method by using phasor dynamical data obtained by a power system simulation package and the phasor measurement system developed in Japan.

収録刊行物

被引用文献 (19)*注記

もっと見る

参考文献 (11)*注記

もっと見る

関連プロジェクト

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ