Improvement of the Evaluation of the Wide Area Power System Stability Based on Multiple Synchronized Phasor Measurements with Observation Sites Changed

Bibliographic Information

Other Title
  • 多地点同期位相計測に基づく電力系統広域安定度推定における観測地点変更時の精度向上
  • タチテン ドウキ イソウ ケイソク ニ モトズク デンリョク ケイトウ コウイキ アンテイド スイテイ ニ オケル カンソク チテン ヘンコウジ ノ セイド コウジョウ

Search this article

Abstract

This paper presents a method for monitoring the power system stability based on wide area phasor measurements. The authors have developed a method for detecting inter-area low-frequency modes from measured small oscillations associated with the load fluctuation by approximating filtered oscillations as a simplified oscillation model. The advantage of this method is that steady state phasor fluctuations are available to evaluate the stability of the power system. In this paper, another type of the filter based on the FFT analysis is developed for improving the accuracy of identified eigenvalues with observation sites changed. The method based on the FFT-based filtering is also applied to extract low-frequency oscillations from phasor data of one observation site. Some numerical analyses demonstrate the effectiveness of the method by using phasor dynamical data obtained by a power system simulation package and the phasor measurement system developed in Japan.

Journal

Citations (19)*help

See more

References(11)*help

See more

Related Projects

See more

Details 詳細情報について

Report a problem

Back to top