Evaluation of Thermal Interruption Capability in SF<sub>6</sub> Gas Circuit Breakers with Re-ignition Voltage and its Application to Experimental Design
-
- Urai Hajime
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Ooshita Youichi
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Koizumi Makoto
- Hitachi Research Laboratory, Hitachi, Ltd.
-
- Tsukushi Masanori
- Japan AE Power Systems Corporation
Bibliographic Information
- Other Title
-
- Evaluation of Thermal Interruption Capability in SF₆ Gas Circuit Breakers with Re-ignition Voltage and its Application to Experimental Design
Search this article
Description
Thermal interruption characteristics of SF6 gas circuit breakers were investigated by voltage measurements around current zero. We found that re-ignition peak voltage in the case of an interruption failure could effectively indicate the thermal interruption capability. The efficiency of interruption to puffer pressure could also be evaluated by analyzing the dependency of re-ignition peak voltage on puffer pressure. This technique was applied to experimental design based on the Taguchi method. We successfully optimized the balance of the puffer pressure build-up performance and thermal interruption efficiency to puffer pressure. Finally we demonstrated that a small size research circuit breaker with self-blast interrupter was able to successfully clear the 90% short line fault interruption duty corresponding to 50kA rating in the thermal interruption region.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 132 (5), 407-414, 2012
The Institute of Electrical Engineers of Japan
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1390282679579938048
-
- NII Article ID
- 10030605420
-
- NII Book ID
- AN10136334
-
- BIBCODE
- 2012IJTPE.132..407U
-
- ISSN
- 13488147
- 03854213
-
- NDL BIB ID
- 023776289
-
- Text Lang
- en
-
- Data Source
-
- JaLC
- NDL Search
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed