三相4線式11.4kV配電方式の適用検討(中性点接地方式の検討)

書誌事項

タイトル別名
  • Analysis of a Neutral Grounding Method for a Three-Phase Four-Wire 11.4kV Distribution System
  • 3ソウ 4センシキ 11 4kV ハイデン ホウシキ ノ テキヨウ ケントウ チュウセイテン セッチ ホウシキ ノ ケントウ

この論文をさがす

抄録

In selection of the neutral grounding method in a three-phase four-wire 11.4kV distribution system, it is necessary to take into consideration voltage rises in lower-voltage line and induced voltage on communication line in case of ground fault. In this paper, we perform EMTP/ATP simulation to select the optimal neutral grounding method and neutral grounding resistance with consideration to above mentioned conditions. The accuracy of the modelling procedure and simulation result is confirmed through verification test performed on test distribution line. As a result, we found 1) that the 11.4kV distribution system should be associated with a resistance single grounding method; and 2) that the neutral grounding resistance should be above 20Ω.