書誌事項
- タイトル別名
-
- Development of an Instrument Used for Hot-line Insulation Diagnosis of House Wiring
- オクナイ ハイセン ノ カッセン ゼツエン シンダン ソウチ ノ カイハツ
この論文をさがす
説明
Recently many electric installations of consumers have been constantly energized. Therefore, the insulation of house wiring is diagnosed by measuring the earth leakage current with a clamp-type current transformer (CT) at the power-source earth line.In this situation there is a technical problem that the earth leakage current measured may include, in addition to active current due to resistances of installations and house wiring to the earth, reactive current due to the capacitance of house wiring to the earth.<br> The authors developed a clamp-type CT equipped with a simple gadget that could remove reactive current(within 4.5mA) component, this provides accurate measurement of the minute active current (beyond 0.01mA). The feature of this instrument is that its measuring technique is based on an algorithm named as hyperbolic measurement method that is capable of arithmetic operation using only scalar quantity when the bias current is made to flow on the CT.<br> As a bias current, a constant current (Ib) in phase with the source voltage and an antiphase constant current (-Ib) are superimposed on CT, respectively, in the first and second computation stages. The scalar values of the resultant currents are used in the computations.<br> This paper describes how to remove electromagnetic noises from the outside as well as the basic theory of the technology developed, composition of an experimentally manufactured instrument, and its performance test results.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 122 (6), 710-718, 2002
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390282679580971008
-
- NII論文ID
- 10008508654
- 10010117015
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 6175494
-
- データソース種別
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可