Result of Lightning Impulse Test for 275kV Full GIS Subetation
-
- Hatano Ryosuke
- Chubu Electric Power Company
-
- Ishikawa Yasuhisa
- Chubu Electric Power Company
-
- Ueda Toshiaki
- Chubu Electric Power Company
-
- Nojima Kenichi
- Toshiba Corporation
-
- Motoyama Hideki
- Central Research Institute of Electric Power Industry
Bibliographic Information
- Other Title
-
- 新設275kV全GIS変電所における実規模雷サージ試験結果
- シンセツ 275kV ゼン GIS ヘンデンショ ニ オケル ジツ キボ カミナリ サージ シケン ケッカ
Search this article
Abstract
This paper describes outline and result of the lightning impulse test for 275kV full GIS substation. The behavior of lightning surges is very important for rational design of substations and low voltage and control circuits inside substations. For above reason, we carried out a lightning impulse test for a new 275kV full GIS substation. In this test, we measured induced voltage of low voltage and control circuits, transient characteristics of grounding mesh, injected voltage and current waveforms, and so on.<br> By investigating these data, we confimed the behavior of lightning surges inside the substation. We also compared simulated waveform by EMTP analysis with measured waveforms. The simulated results agreed well with the measured results.
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 122 (10), 1110-1119, 2002
The Institute of Electrical Engineers of Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390282679581486464
-
- NII Article ID
- 130006841262
- 10010002756
-
- NII Book ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL BIB ID
- 6316349
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed