Field Test of 70MW Class Superconducting Generator in The Mode of Synchronous Condenser

DOI DOI Web Site Web Site Web Site View 1 Remaining Hide 1 Citations 16 References Open Access

Bibliographic Information

Other Title
  • 7万kW級超電導発電機の電力系統における同期調相機運転試験
  • 7マンkWキュウ チョウデンドウハツデンキ ノ デンリョク ケイトウ ニ オケル ドウキチョウソウキ ウンテン シケン
  • Field test of a 70‐MW‐class superconducting generator in the mode of a synchronous condenser

Search this article

Description

In order to study the basic performance of the superconducting generator in the actual electric power system, the quick response excitation type generator was connected to 77kV commercial power grid of the KANSAI Electric Power Co., Inc. In the test, the model machine was operated as a rotary condenser supplying about leading 40MV ar to the electric power system. In the tests, the model machine operated stably. The results show that the superconductig generator has effects for stabilizing voltage fluctuations of electric power system and also for reducing shunt reactor.

Journal

Citations (1)*help

See more

References(16)*help

See more

Details 詳細情報について

Report a problem