- Overvoltage Phenomena Caused by Disconnecting Motor-Loads on Power Line with Open-Phase
- ケッソウジ ノ デンドウキ フカ シャダン ニ ヨル デンアツ ジョウショウ
- Overvoltage phenomena caused by disconnecting motor-loads on power lines with open-phase
この論文をさがす
説明
This paper describes overvoltage caused by disconnecting a lot of motor-loads on a power distribution line with power-factor-correcting capacitors during a transmission line open-phase. The overvoltage phenomena are studied by a field test, a steady-state analysis and a transient analysis. Experimental results show that the line-to-line voltage on a 6.6kV distribution line with an open-phase 22kV transmission line amounts to 1.7 per unit. The overvoltages are caused by two types of resonance. One is the linear circuit resonance between the power-factor-correcting capacitors and the secondary side impedance of motors. The difference between positive components and negative ones of the impedance produces the resonance. The other is the non linear circuit resonance between the power-factor-correcting capacitors and the saturated reactances of a transformer.
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 113 (6), 653-658, 1993