真空加熱分離方式による柱上変圧器構成材からのPCB除去に関する実証的研究

書誌事項

タイトル別名
  • Proving Test on Removal of PCB from Pole Transformer by Vacuum Heating Separation Method
  • シンクウ カネツ ブンリ ホウシキ ニヨル チュウジョウ ヘンアツキ コウセイ

この論文をさがす

説明

In 1989, PCB was found in recycled insulation oils used in some pole transformers in trace of 50 mg per one kg of insulation oil, , prompting quick establishment of their safe separation method. One of prospective methods for removing such recycled insulation oils, ets. as attached and impregnated to the transformer coils may be a vacuum heating separation method which heats and vaporizes PCB under vacuum condition for separation. A proving test for applicability of the specific vacuum heating separation method was carried out with actually used transformers, which confirmed that residual PCB on coils was minimized less than a quantitative determination lower limit of 0.05 mg per one kg of insulation oil under the following standard applicable condition : vacuum of lower than 0.05 Torr ; heating temperature of 200°C; and vacuum holding time of 10 hrs., thus successfully proving insignificant effect of the treatment facility and the method on environment.