超電導薄膜限流器とテープ巻線型限流器の導体コスト比較

書誌事項

タイトル別名
  • Comparison of Estimated Conductor Costs between a Superconducting Thin-film Fault-current Limiter (FCL) and a Coated-conductor-based Superconducting FCL
  • チョウデンドウハクマクゲンリュウキ ト テープ マキセンガタゲンリュウキ ノ ドウタイ コスト ヒカク

この論文をさがす

抄録

We recently proposed a new design for a high-temperature superconducting thin-film fault-current limiter (FCL), which uses high-resistivity Au-Ag alloy shunt layers instead of the pure gold (or silver) shunt layers conventionally used. Due to the much larger resistance of the Au-Ag alloy layers, the FCL elements withstood very high electric fields (> 40 Vpeak/cm), and realized a very high switching power density, ∼2.0 kVA/cm2. The composition of our FCL element is very simple, and the achieved power density is more than five times higher than conventional devices, which leads to a dramatic reduction in the amount of expensive superconducting thin films required. Similarly, Kinder et al. recently proposed a new coated-conductor-based FCL element, which achieved a relatively high electric field of 2.7 Vpeak/cm. We estimated the cost of our thin-film FCL elements used in a typical 6.6 kV FCL that is introduced in a distributed power supply site. We also estimated the cost of coated conductors used to produce the FCL, and compared the two.

収録刊行物

  • 低温工学

    低温工学 41 (9), 397-404, 2006

    公益社団法人 低温工学・超電導学会 (旧 社団法人 低温工学協会)

被引用文献 (2)*注記

もっと見る

参考文献 (30)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ