Elucidation of DC Magnetic Deviation in Converter Transformers Used for a Self-Commutated BTB System during Single-Line-to-Ground Faults

Bibliographic Information

Other Title
  • 一線地絡時に自励式BTBの変換器用変圧器に発生する直流偏磁現象の解明
  • イッセン チラクジ ニ ジレイシキ BTB ノ ヘンカンキヨウ ヘンアツキ ニ ハッセイスル チョクリュウ ヘンジ ゲンショウ ノ カイメイ

Search this article

Abstract

This paper deals with a 50-MW self-commutated BTB (Back-To-Back) system intended for power-flow control between transmission networks. It focuses on the dynamic behavior of the BTB system during single-line-to-ground (SLG) faults. During an SLG fault, a dc magnetic deviation appears in the converter-transformers used for the BTB system just after the occurrence and restoration of the fault. It is indispensable to understand an amount of deviation because it may bring magnetic saturation as well as a large amount of magnetizing current to the transformers. This paper derives theoretical equations related to the deviation during the SLG fault. The theoretical analysis developed in this paper would make significant contributions to designing the transformers.