Elucidation of DC Magnetic Deviation in Converter Transformers Used for a Self-Commutated BTB System during Single-Line-to-Ground Faults
-
- Hagiwara Makoto
- Electrical Engineering, Tokyo Institute of Technology
-
- Pham Phuong Viet
- Electrical Engineering, Tokyo Institute of Technology
-
- Akagi Hirofumi
- Electrical Engineering, Tokyo Institute of Technology
Bibliographic Information
- Other Title
-
- 一線地絡時に自励式BTBの変換器用変圧器に発生する直流偏磁現象の解明
- イッセン チラクジ ニ ジレイシキ BTB ノ ヘンカンキヨウ ヘンアツキ ニ ハッセイスル チョクリュウ ヘンジ ゲンショウ ノ カイメイ
Search this article
Abstract
This paper deals with a 50-MW self-commutated BTB (Back-To-Back) system intended for power-flow control between transmission networks. It focuses on the dynamic behavior of the BTB system during single-line-to-ground (SLG) faults. During an SLG fault, a dc magnetic deviation appears in the converter-transformers used for the BTB system just after the occurrence and restoration of the fault. It is indispensable to understand an amount of deviation because it may bring magnetic saturation as well as a large amount of magnetizing current to the transformers. This paper derives theoretical equations related to the deviation during the SLG fault. The theoretical analysis developed in this paper would make significant contributions to designing the transformers.
Journal
-
- IEEJ Transactions on Industry Applications
-
IEEJ Transactions on Industry Applications 127 (9), 1013-1022, 2007
The Institute of Electrical Engineers of Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390282679634477568
-
- NII Article ID
- 10019521225
-
- NII Book ID
- AN10012320
-
- ISSN
- 13488163
- 09136339
-
- NDL BIB ID
- 8935054
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed