Design and Performance of a Transformerless Shunt Hybrid Active Filter for Installation on a 6.6-kV Power Distribution System
-
- Inzunza Rubén
- Tokyo Institute of Technology
-
- Akagi Hirofumi
- Tokyo Institute of Technology
Search this article
Abstract
This paper presents the analysis and design of a shunt hybrid active filter for harmonic damping in a 6.6-kV power distribution system. This hybrid filter has been proposed and tested experimentally with a 200-V, 20-kW laboratory system, showing good damping performance. Another possible solution for harmonic damping is to install a shunt pure active filter at the end of a feeder. However, the pure filter is too costly and bulky to be installed in a 6.6-kV system. This paper discusses the design criteria for a hybrid filter intended for installation on a 6.6-kV power distribution system. Detailed comparisons between the pure filter and the hybrid filter are also included as a foundation for the design of the hybrid filter. The performed design confirms the feasibility of installation of the hybrid filter on a 6.6-kV power distribution system.
Journal
-
- IEEJ Transactions on Industry Applications
-
IEEJ Transactions on Industry Applications 126 (4), 497-503, 2006
The Institute of Electrical Engineers of Japan