Closing Surge and Surge Propagation at SHINKANSEN Changeover Section
-
- Hayashiya Hitoshi
- Technical Center, R&D Center of JR East Group
-
- Ajiki Koji
- Power Supply Technology Division, RTRI
Bibliographic Information
- Other Title
-
- 新幹線切替セクションにおける無負荷投入過電圧とサージ伝搬
- シンカンセン キリカエ セクション ニ オケル ムフカ トウニュウ カデンアツ ト サージ デンパン
Search this article
Description
In some substations and sectioning posts of Shinkansen power system in JR East area, the electrical transient phenomena when the Shinkansen train passes through the changeover section are reported during the last a few years. In this paper, the closing surge phenomena of the Shinkansen changeover section are elucidated based on both the detail measurement of the surge phenomena at substations and computer simulation. It is clarified that the surge propagation and the reflection at open end of the contact wire system cause the over-voltage at changeover section and result in the discharge of the lightning arresters at some substations.
Journal
-
- IEEJ Transactions on Industry Applications
-
IEEJ Transactions on Industry Applications 126 (3), 322-329, 2006
The Institute of Electrical Engineers of Japan
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1390282679635674752
-
- NII Article ID
- 10017276585
-
- NII Book ID
- AN10012320
-
- ISSN
- 13488163
- 09136339
-
- NDL BIB ID
- 7857924
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- NDL Search
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed