ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH系フィンチューブ式吸着器の性能評価

書誌事項

タイトル別名
  • Evaluation of a Fin and Tube Type Adsorber/Desorber Heat Exchanger using =ACF/C<Sub>2</Sub>H<Sub>5</Sub>OH Pair
  • ACF/C2H5OH系フィンチューブ式吸着器の性能評価
  • ACF C2H5OHケイ フィンチューブシキ キュウチャクキ ノ セイノウ ヒョウカ

この論文をさがす

抄録

This study deals with the experiment to clarify the characteristics of adsorption refrigeration system employing activated carbon fiber (ACF) and ethanol pair and to evaluate the performance of adsorber/desorber heat exchanger defined by two kind of index to the system performance. The experiments are carried out by varying system running parameters such as regeneration temperature for adsorber, ethanol temperature in the evaporator, pre-heating/cooling cycle time, adsorption/desorption cycle time. Regeneration temperature for adsorber is from 60 to 90 °C and ethanol temperature is from 0 to 20 °C and pre-heating/cooling cycle time is 60 and 120 second and adsorption/desorption cycle time is from 120 to 300 second. Results show that the system can be operated with regeneration temperature of 60 °C and the system performance improves with increase of ethanol temperature. It is also found that the system performance is affected by regeneration temperature for adsorber and the pre-heating/cooling cycle time and adsorption/desorption cycle time.