- Heat Transfer and Pressure Drop for Flow Boiling of Non-Azeotropic Refrigerant Mixtures of HFC-32/HFC-125/HFC-134a and HFC-32/HFC-134a in Horizontal Tubes
- ヒ キョウフツ コンゴウ レイバイ HFC-32 HFC-125 HFC-13
この論文をさがす
説明
Experiments were performed on heat transfer and pressure drop for flow boiling of two non-azeotropic refrigerant mixtures of HFC-32/HFC-125/HFC-134a and HFC-32/HFC-134a at respectively certain compositions,which are expected to be alternatives to HCFC-22,in horizontal smooth and internally,spirally grooved tubes. Almost the same local heat transfer coefficients were obtained for both the mixtures in each tube. In the smooth tube,in the region where nucleate boiling contributes substantially to the heat transfer,the heat transfer coefficients for the mixtures were reduced down to about two-thirds of the value for HCFC-22,due to the effect of a mass transfer resistance on the heat transfer,while they were approximately equal to those for HCFC-22 in the forced convection dominated region. With the grooved tube,the heat transfer was enhanced over the smooth tube,but the enhancement was smaller than that for HCFC-22. In both the tubes,frictional pressure drops for the binary mixture were generally a few to 20 percent higher than those for the ternary mixture and the pure refrigerant,corresponding to the difference in the vapor density.
収録刊行物
-
- 日本冷凍空調学会論文集
-
日本冷凍空調学会論文集 14 (1), 39-45, 1997
公益社団法人 日本冷凍空調学会
- Tweet
キーワード
詳細情報 詳細情報について
-
- CRID
- 1390282679643496192
-
- NII論文ID
- 10002713961
-
- NII書誌ID
- AA11125910
-
- ISSN
- 2185789X
- 13444905
-
- NDL書誌ID
- 4184405
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- NDL
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可