HFC系混合冷媒を用いた蒸気圧縮式ヒートポンプシステムの性能評価

書誌事項

タイトル別名
  • The Performance Evaluation of Vapor Compression Heat Pump System Using HFC Alternative Refrigerant Mixtures
  • HFC系混合冷媒を用いた蒸気圧縮式ヒートポンプシステムの性能評価--冷房モードの場合
  • HFCケイ コンゴウ レイバイ オ モチイタ ジョウキ アッシュクシキ ヒートポンプ システム ノ セイノウ ヒョウカ レイボウ モード ノ バアイ
  • -冷房モードの場合-
  • -In the case of cooling mode-

この論文をさがす

抄録

This paper deals with an experimental study on the performance evaluation of heat pump systems using HFC alternative refrigerants. The tested heat pump systems are modified from the R22 use to alternative refrigerants. Refrigerant mixtures of R410A, R407C. R32/125 and R32/134a are tested. where R410A and R407C launched into global market recently. Pure refrigerants of R22, R32, R125 and R134a are also tested. <br>The experimental results of alternative refrigerants are evaluated in comparison with the result of R22, and the following are confirmed : (1) the performance of R32 is the highest. (2) adding R125 to R32 and R32/134a results into the deterioration of the performance, (3) the use of counter flow-like heat exchangers for a zeotropic refrigerant mixtures are effective, and (4) in case of R410A. the modification of the compressor to fit operating pressure heightens the performance. The effects of the performance of components on the COP are also analyzed based on the measured thermodynamic states at both ends of components in the system. Then, it is clarified that the most effective factor is irreversibility of compressors and the following is the pressure drop in low pressure side including the evaporator and the suction pipe.