This paper aims at developing an optimal design procedure of a hybrid air-conditioning system of cooled ceiling (CC) and displacement ventilation (DV) systems to meet the demand of both thermal comfort and air quality environment in the occupied zone. A series of experiments were carried out using a hypothetical office room to obtain data of vertical air temperature distribution, local ventilation efficiency and thermal comfort level affected by the various setting parameters of the air-conditioning system. Importance is stressed on the choice of CC cooling output ratio η to the vertical temperature difference of occupied zone and thermal comfort. Based on the subjective sensory experiments, optimal temperature difference of occupied zone is proposed at 2.5℃. Present work was summarized as a design diagram that can be used to determine the η value to realize the highest ventilation efficiency within acceptable range of vertical air temperature difference.