- 西岡 利光
- 大阪市立大学工学部建築学科
書誌事項
- タイトル別名
-
- STUDIES ON PERFORMANCE OF CLEANROOM USING DECAY OF PARTICLE : Concentration for case of unidirectional flow type
- セイジョウド タチアガリ トクセイ ニ ヨル クリーンルーム ノ セイノウ ヒョウカ ニ カンスル ケンキュウ イッポウ コウリュウ ホウシキ ノ バアイ
この論文をさがす
説明
The air cleaning ability of a unidirectional flow cleanroom system is examined experimentally in regard to various air-supply velocities, the size of the vent of the ceiling and of the floor and the relations between them. The change of particle concentration is referred to as the 'decay of particle concentration' judged from the point when the system begins operation. The pattern and the time of this decay indicates the system's air cleaning ability. The experiment shows that although the configuration of the cleanroom is a unidirectional flow, the property of controlling contamination is in three degrees, namely, unidirectional flow, 'perfect diffusion', and 'imperfect discharge' according to the velocity. The latter two are referred to as non-unidirectional. Clean-up time is calculated using two kind of equations. The lower limit of the vent's size is obtained. For the ceiling inlet, 50% of the size ratio constitutes the lower limit necessary to maintain the cleanliness class 5 in JIS B 9920, to the contrary to the limit of 14% for the floor outlet.
収録刊行物
-
- 日本建築学会計画系論文集
-
日本建築学会計画系論文集 65 (527), 37-44, 2000
日本建築学会