換気回路網計算による住宅の新鮮空気量充足度の評価 : 集合住宅を対象とした計算

書誌事項

タイトル別名
  • EVALUATION OF FULFILLMENTS FOR REQUIRED FRESH AIR SUPPLY RATE OF HOUSES BY USING NETWORK MODEL : Results of calculations of an apartment house
  • カンキ カイロモウ ケイサン ニ ヨル ジュウタク ノ シンセン クウキリョウ ジュウソクド ノ ヒョウカ シュウゴウ ジュウタク オ タイショウ ト シタ ケイサン

この論文をさがす

抄録

Evaluation of the ventilation performance of buildings, especially for residential houses, is complicated because many rooms are connected intricately and there are many factors which influence ventilation condition. The purpose of this study is to clarify the relations among ventilation performance, ventilation systems, air tightness of house and other factors, using Supply Rate Fulfillment index and network flow model. SRF index can treat transferred air, which passed through other rooms, as certain potential of fresh air. Following conclusions are obtained for the ventilation performance evaluation of different systems in an apartment house. ・Under the condition of using F_<co>-class plywood and applying ventilation requirement in the Japanese energy conservation standards (1999), the concentration of formaldehyde will be below the WHO standard. ・The range of wind velocity and wind pressure, in which Overall Supply Rate Fulfillment index complying with ventilation requirement for individual rooms in the Japanese energy conservation standards stay lager than 0.8,are shown.