差動変流器による自励交流発電機の並列運転について
書誌事項
- タイトル別名
-
- On the Parallel Operation of Self-excited A. C. Generators with Differential Current Transformer
この論文をさがす
説明
Various cross current compensators (CCC) are used to restrain wattless cross current which flows between generators connected parallel in such as the Ship's A. C. power system.<BR>When load power factor is low, these CCC's generally reduce the bus voltage, and thus the effect of CCC's opposes to the effect of the automaticvoltage regulator (AVR) . This means that the more cross current compensation is intended, the worse becomes the regulation of the main bus voltage, and the regulation will be larger than that at single operation.<BR>We have used the differential current transformer (DCT) for these CCC circuits, and have confirmed by experiments on the marchant ship that the voltage drop at the parallel operation are remarkably reduced.<BR>We also confirmed that the analytical results of the effects of the DOT Constant coincide to the experimental results.<BR>The DCT can be used for any AVR system and the voltage regulation of the bus can be kept within ± 1 % in both cases of single and parallel operation by using the DCT.
収録刊行物
-
- 日本舶用機関学会誌
-
日本舶用機関学会誌 4 (7), 383-390, 1969
公益社団法人 日本マリンエンジニアリング学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390282680136676352
-
- NII論文ID
- 130001336683
-
- ISSN
- 18844758
- 03883051
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可