吸収式冷温水機のファジィ制御系に関する実験的検討

書誌事項

タイトル別名
  • Experimental Study of Control Systems Using Fuzzy Inference for Absorption Chillers/Heaters
  • キュウシュウシキ レイオンスイキ ノ ファジイ セイギョケイ ニ カンスル ジ

この論文をさがす

抄録

Generally speaking, it is difficult to make a model which satisfies completely all the characteristics for absorption chillers/heaters, therefore PID control is often used. In this paper, to improve energy saving with stable and fast response, we apply fuzzy control using well-known characteristics as knowledge for fuzzy inference to absorption chillers/heaters.<BR>Consequently it is verified with experiments on a 100 USRton double stage absorption chillers/heaters that proposed multi-input fuzzy controlled system is better then PID controlled system with gains adjusted by fuzzy interence, when refrigeration load is quickly changed like step change, start-up and temperature of cooling water increases.