A pressurized smoke control system was employed in the 25 stories' high-rise apartment building named "Akasaka Tameike Tower." We have conducted a performance examination test of the system. From the results of the test, it was confirmed that: 1) the pressure differences at the evacuation routes agreed with the requirements for smoke prevention; and 2) door opening force in operating the system was low enough for the children to open the doors. Furthermore, effective flow areas of some architectural components, such as doors and pressure adjusting openings, were measured and design data for simulating the pressure difference of the system were collected.