書誌事項
- タイトル別名
-
- PERFORMANCE EXAMINATION TEST OF PRESSURIZED SMOKE CONTROL SYSTEM FOR A HIGH-RISE APARTMENT BUILDING
- コウソウ シュウゴウ ジュウタク ニ オケル カアツボウエン システム ノ セイノウ カクニン ジッケン
この論文をさがす
説明
A pressurized smoke control system was employed in the 25 stories' high-rise apartment building named "Akasaka Tameike Tower." We have conducted a performance examination test of the system. From the results of the test, it was confirmed that: 1) the pressure differences at the evacuation routes agreed with the requirements for smoke prevention; and 2) door opening force in operating the system was low enough for the children to open the doors. Furthermore, effective flow areas of some architectural components, such as doors and pressure adjusting openings, were measured and design data for simulating the pressure difference of the system were collected.
収録刊行物
-
- 日本建築学会技術報告集
-
日本建築学会技術報告集 8 (15), 137-142, 2002
一般社団法人 日本建築学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390282680149171840
-
- NII論文ID
- 110004062177
-
- NII書誌ID
- AN10531441
-
- ISSN
- 18818188
- 13419463
-
- NDL書誌ID
- 6206013
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- NDLサーチ
- Crossref
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可