OPERATION RESULTS OF DHC PLANTS IN EXPO 2005
-
- NAKAJIMA Yusuke
- Dept. of Design in Architecture and Urbanism, Kogakuin Univ.
-
- YAMADA Masaya
- Graduate School, Kogakuin Univ.
-
- TAKAGUCHI Hiroto
- Dept. of Architecture, Waseda Univ.
Bibliographic Information
- Other Title
-
- 愛知万博における地域冷暖房プラント運転実績調査
- アイチ バンパク ニ オケル チイキ レイダンボウ プラント ウンテン ジッセキ チョウサ
Search this article
Abstract
EXPO2005 was held from Mar. 25 to Sep. 25 in 2005. In this EXPO Nagakute area, air-conditioning energy were supplied from five DHC plants. We had recorded air-conditioning energy, gas, power, and upper and lower water consumption in this area. In this study, we chiefly analyze the operation results of these DHC plants. As a results, main three plants had tended to operate in a lot of numbers of the refrigerating machine for the load. In that situation, plant No. 6 which was subdivided to four showed better COP value, and importance of quipment composition of plants was confirmed. And, it was problem that excessive load calculation of enterprise pavilions influenced the plant load factor decrease.
Journal
-
- Journal of Environmental Engineering (Transactions of AIJ)
-
Journal of Environmental Engineering (Transactions of AIJ) 73 (624), 237-243, 2008
Architectural Institute of Japan
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1390282680175699072
-
- NII Article ID
- 110006571121
-
- NII Book ID
- AA11830377
-
- ISSN
- 1881817X
- 13480685
-
- NDL BIB ID
- 9379342
-
- Data Source
-
- JaLC
- NDL
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed