STUDY ON APPLIKABILITY OF DETACHED-EDDY SIMULATION FOR WIND INDUCED VENTILATION ANALYSIS
-
- HASAMA Takamasa
- Dept. of Architecture, Faculty of Eng., the Univ. of Tokyo
-
- KATO Shinsuke
- Institute of Industrial Science, the Univ. of Tokyo
-
- OOKA Ryozo
- Institute of Industrial Science, the Univ. of Tokyo
Bibliographic Information
- Other Title
-
- 通風換気性状予測に対するDetached-eddy simulationの適用に関する検討
- ツウフウ カンキ セイジョウ ヨソク ニ タイスル Detached eddy simulation ノ テキヨウ ニ カンスル ケントウ
Search this article
Abstract
To examine the applicability of DES for building ventilation analysis, DES and LES were performed on a flow with a building having a single-sided opening. We also made simulations of the concentration flowfield on the same analysis model. Three types of calculation cases (1. LES calculation with coarsen grid, 2. DES calculation with coarsen grid, 3. Reference LES calculation with fine grid) were performed. It is clarified that DES could predict the unsteady and time average flow feature like the LES. However, DES tends to reduce the Grid-scale components compared with LES. As the result, the air exchange rate in LES was lower than LES.
Journal
-
- Journal of Environmental Engineering (Transactions of AIJ)
-
Journal of Environmental Engineering (Transactions of AIJ) 72 (617), 39-45, 2007