立方体正味放射計を用いた床冷房室内の周壁熱流束に関する実験的研究

書誌事項

タイトル別名
  • EXPERIMENTAL STUDY ON HEAT FLUX THROUGH SURROUNDING SURFACES IN A ROOM WITH FLOOR COOLING USING A CUBIC NET RADIOMETER
  • リッポウタイ ショウミ ホウシャケイ オ モチイタ ユカレイボウ シツナイ ノ シュウヘキ ネツリュウソク ニ カンスル ジッケンテキ ケンキュウ

この論文をさがす

説明

Surface temperatures of the surrounding six walls were estimated on the measurement of plane radiant temperature on six surfaces of the cube using a cubic net radiometer. Conduction heat flux of some surface of the surrounding walls was measured by heat flow meter. Radiation heat flux on the surface of heat flow meter was estimated using angle factors and surface temperatures of the surrounding walls. Convection heat flux was calculated as the heat balance of the surface of heat flow meter. The effective radiant field as the error in use of the overall heat transfer coefficient was studied and indicated never to be ignored in the simple calculation of heat flow on the wall surface.