書誌事項
- タイトル別名
-
- STUDY ON PREDICTION OF VENTILATION IN WHOLE HIGH-RISE BUILDING
- 高層ビル全体の換気性状の予測に関する研究 : エレベーター扉前後の差圧の実測値と計算値の比較
- コウソウ ビル ゼンタイ ノ カンキ セイジョウ ノ ヨソク ニ カンスル ケンキュウ : エレベーター トビラ ゼンゴ ノ サアツ ノ ジッソクチ ト ケイサンチ ノ ヒカク
- エレベーター扉前後の差圧の実測値と計算値の比較
- Comparison between measured and calculated values of pressure difference at elevator door
この論文をさがす
説明
In winter, environmental problems caused by the stack effect occur in high-rise buildings. In order to prevent the stack effect, it is necessary to estimate the behavior of the natural ventilation quantitatively for a whole building. In this study, we measured pressure difference at elevator doors in an actual building through one winter, and at the same time, the numerical analysis by the airflow network model were performed. As the results, the calculated pressure differences at the elevator door on the top and bottom floor showed good agreement with the measured values for both nighttime and commuting time.