G-45 ソーラーチムニーを主体とする環境配慮型大学校舎の設備システムに関する研究 : (第4報)チムニーによる中間期、冬期の自然換気量の測定と評価
書誌事項
- タイトル別名
-
- G-45 Natural Ventilation System for the Ecological College Building using Solar Chimneys : (Part4)Measurement and Evaluation of Ventilation Rate in Spring, Autumn and Winter
説明
In addition to the former report, Natural ventilation rate using solar chimneys in a sustainable college building NO.14 was measured using tracer gas method in Spring, Autumn and Winter. And air change rate was about 0.3〜0.5times/hour. At the same time, temperature distribution in the building, air movements and weather condition are also measured. Those data are used to multi-rooms ventilation calculation. As a result of repeating improvements of the calculation model, the calculation result came to accord with measured value well.
収録刊行物
-
- 空気調和・衛生工学会大会 学術講演論文集
-
空気調和・衛生工学会大会 学術講演論文集 2006.2 (0), 1409-1412, 2006