G-19 大型家電量販店舗における空調負荷の実測 : 温暖地と寒冷地の比較
書誌事項
- タイトル別名
-
- G-19 Measurements of Thermal Loads in Large Electric Home Appliance Retail Stores, : Comparison of Warm and Cold areas
抄録
We report the results of measurements of indoor thermal loads in two large electric-home-appliance retail stores, in which EHP and/or GHP are used for air-conditioning, with attention to the influence of outdoor air temperature distributions on thermal load characteristics. Based on the measured results we made the indoor thermal load model of this type of stores ith large indoor heat sources. We calculated the annual thermal loads in three cities with different meteorological conditions using this thermal load model and Expanded AMeDAS weather data, and found that the cooling load was as larger as the heating load even in a northern city in Japan.
収録刊行物
-
- 空気調和・衛生工学会大会 学術講演論文集
-
空気調和・衛生工学会大会 学術講演論文集 2010.1 (0), 573-576, 2010
公益社団法人 空気調和・衛生工学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390282680218898816
-
- NII論文ID
- 110009780342
-
- ISSN
- 24242179
- 18803806
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- CiNii Articles
-
- 抄録ライセンスフラグ
- 使用不可