OS2-22 アンモニア/水を用いた海洋温度差発電システムにおける組成の影響(OS2 自然エネルギー,循環型社会における動力エネルギー技術)

書誌事項

タイトル別名
  • OS2-22 Effect of Mass Fraction of Ammonia on OTEC Systemwith Ammonia/water Mixture as Working Fluid

抄録

The Uehara cycle utilizes ammonia/water mixture as working fluid. For the efficient ocean thermal energy conversion (OTEC) system, nonazeotropic mixtures were utilized as working fluid. This paper describes the effect of mass fraction of ammonia on the cycle. As a result, the overall heat transfer coefficient of evaporator and condenser were increased with evaporator inlet mass fraction of ammonia. And that increased the turbine power out put and cycle thermal efficiency. Consequently, the influence of the additional water on the system was less effective for our plant in this experimental condition. Since we should improve the system to advantage of the mixture.