- Oshima Toshio
- Himeji Inst. of Tech.
-
- Iuchi Satoru
- Himeji Inst. of Tech.
-
- Yoshida Akira
- Kawaki Setssubi Kogyo Co., Ltd.
-
- Takamatsu Katsumi
- Nikko Co., Ltd.
Bibliographic Information
- Other Title
-
- 噴霧水蒸発型空冷熱交換器の計算法
Abstract
An calculation method for air cooled exchangers with water spray is presented.The phenomena of vaporization of water spray into air are analysed in the viewpoint of simultaneous heat and mass transfer on finned tubes.In the calculation method, it is assumed that air flow is saturated through the exchanger and finned tube surfaces are wetted homogeneously. Under suitable spray conditions, the transfer area calculated by this method are good agreed with the area of experimental apparatus.This indicates that the calculation method is proper to commercial exchanger design.
Journal
-
- Chemical engineering
-
Chemical engineering 36 (5), 539-546,a1, 1972
The Society of Chemical Engineers, Japan
- Tweet
Details 詳細情報について
-
- CRID
- 1390282681428589952
-
- NII Article ID
- 130003931430
-
- ISSN
- 03759253
-
- Text Lang
- ja
-
- Data Source
-
- JaLC
- Crossref
- CiNii Articles
-
- Abstract License Flag
- Disallowed