A Study on the Way of Maintenance of Sanitary Environment in Medical Facilities : Part1-Outline of the Investigation and Legal Measurement Results on Indoor Air Environment

Bibliographic Information

Other Title
  • 病院施設における室内環境の衛生管理に関する研究 : 第1報-空気環境法定測定に準じた実態調査
  • ビョウイン シセツ ニ オケル シツナイ カンキョウ ノ エイセイ カンリ ニ カンスル ケンキュウ ダイ1ポウ クウキ カンキョウ ホウテイ ソクテイ ニ ジュンジタ ジッタイ チョウサ

Search this article

Description

It is important to maintain indoor air and sanitary environments in waiting lounges, office rooms and medical wards of medical facilities. However, Japan has neither environmental nor hygiene law for medical facilities. In this study, the way of the maintenance of sanitary environments in medical facilities was examined. This part reported the measurement results of air temperature, relative humidity, airflow rate velocity, CO, CO_2, PM and formaldehyde concentrations in waiting lounges, office rooms and medical wards of 16 medical facilities in winter and summer. As a result, relative humidity values in most part of the rooms in winter were lower than 40%Rh. The CO_2 concentrations in the waiting lounges that had a lot of people were remarkably high. It can be presumed that the capacities of the ventilating rate were insufficient.