- 【Updated on May 12, 2025】 Integration of CiNii Dissertations and CiNii Books into CiNii Research
- Trial version of CiNii Research Knowledge Graph Search feature is available on CiNii Labs
- Suspension and deletion of data provided by Nikkei BP
- Regarding the recording of “Research Data” and “Evidence Data”
A Study on the Way of Maintenance of Sanitary Environment in Medical Facilities : Part1-Outline of the Investigation and Legal Measurement Results on Indoor Air Environment
-
- KAGI Naoki
- National Institute of Public Health
-
- YANAGI U
- National Institute of Public Health
-
- IKEDA Koichi
- National Institute of Public Health
-
- NISHIMURA Naoya
- Shibaura Institute of Technology
-
- YOSHINO Hiroshi
- Tohoku University
-
- OBATA Michio
- Building Management Education Center
-
- SAITO Hideki
- Building Management Education Center
-
- SAITO Keiko
- Building Management Education Center
-
- KAMAKURA Ryota
- Building Management Education Center
Bibliographic Information
- Other Title
-
- 病院施設における室内環境の衛生管理に関する研究 : 第1報-空気環境法定測定に準じた実態調査
- ビョウイン シセツ ニ オケル シツナイ カンキョウ ノ エイセイ カンリ ニ カンスル ケンキュウ ダイ1ポウ クウキ カンキョウ ホウテイ ソクテイ ニ ジュンジタ ジッタイ チョウサ
Search this article
Description
It is important to maintain indoor air and sanitary environments in waiting lounges, office rooms and medical wards of medical facilities. However, Japan has neither environmental nor hygiene law for medical facilities. In this study, the way of the maintenance of sanitary environments in medical facilities was examined. This part reported the measurement results of air temperature, relative humidity, airflow rate velocity, CO, CO_2, PM and formaldehyde concentrations in waiting lounges, office rooms and medical wards of 16 medical facilities in winter and summer. As a result, relative humidity values in most part of the rooms in winter were lower than 40%Rh. The CO_2 concentrations in the waiting lounges that had a lot of people were remarkably high. It can be presumed that the capacities of the ventilating rate were insufficient.
Journal
-
- Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan
-
Transactions of the Society of Heating,Air-conditioning and Sanitary Engineers of Japan 33 (137), 39-46, 2008
The Society of Heating, Air-Conditioning & Sanitary Engineers of Japan
- Tweet