書誌事項
- タイトル別名
-
- A SVR Control Method with Switching Multiple LDC Parameters Using Measurement Data of Distribution Systems
- ハイデン ケイトウ ノ センサ ケイソク ジョウホウ オ モチイタ フクスウ ノ セイテイチ キリカエ ニ ヨル SVR サイテキ セイギョ シュホウ ノ ケントウ
この論文をさがす
説明
<p>The voltage regulation in distribution systems becomes more important these days due to the more complicated power flow profile caused by the integration of variable renewable energy sources such as photovoltaic (PV). Step voltage regulator (SVR) and load ratio controlled transformer (LRT) have been mainly used for the voltage regulation conventionally based on decentralized control methods using line drop compensation (LDC) logic for estimation of voltage drop at secondary side of the SVR. Here, it has been required for distribution system operator to determine LDC parameters properly to estimate the voltage drop based on locally measured information. Hence, in this paper, we proposed an advanced LDC logic in which the parameters can be flexibly switched based on the power flow conditions. The effectiveness of the proposed method was verified using 41-node distribution system model with PV.</p>
収録刊行物
-
- 電気学会論文誌B(電力・エネルギー部門誌)
-
電気学会論文誌B(電力・エネルギー部門誌) 141 (5), 374-383, 2021-05-01
一般社団法人 電気学会
- Tweet
詳細情報 詳細情報について
-
- CRID
- 1390287907270260608
-
- NII論文ID
- 130008033171
-
- NII書誌ID
- AN10136334
-
- ISSN
- 13488147
- 03854213
-
- NDL書誌ID
- 031499009
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- NDLサーチ
- Crossref
- CiNii Articles
- OpenAIRE
-
- 抄録ライセンスフラグ
- 使用不可