Study on Energy Consumption and Indoor Thermal Environment of Floor Heating System using Exhausted Heat from PEFC-CGS

DOI HANDLE Web Site Open Access

Bibliographic Information

Other Title
  • PEFC-CGSと温水式床暖房の併用効果に関する研究 : 省エネルギー効果と室内温熱環境について
  • PEFC CGS ト オンスイシキ ユカダンボウ ノ ヘイヨウ コウカ ニ カンスル ケンキュウ ショウエネルギー コウカ ト シツナイ オンネツ カンキョウ ニ ツイテ

Search this article

Abstract

We have been developed the numerical simulation program to calculate the primary energy consumption of housing Polymer Electrolyte Fuel Cell Co-Generation System(PEFC-CGS) combined with floor heating of warm water type. In this program, the floor heating has been modeled with the piping pitch of warm water by using the fin efficiency. The indoor temperature has been controlled by Predicted Mean Vote(PMV) for over minus 0.5. As the results of this simulation, it is clarified that the floor heating has had effected the indoor by thermal radiation from floor surface and that the primary energy consumption has been reduced up to 5% in winter when PEFC-CGS is combined with the floor heating of warm water type.

Journal

  • 都市・建築学研究

    都市・建築学研究 11 127-136, 2007-01-15

    Faculty of Human-Environment Studies, Kyushu University

Related Projects

See more

Details 詳細情報について

Report a problem