位相分解部分放電パターン再構築とニューラルネットワークによる変電所の絶縁診断

書誌事項

タイトル別名
  • Examination of Insulation Diagnosis in Substation by Neural Network with Phase-resolved Partial Discharge Pattern Reconstruction
  • イソウ ブンカイ ブブン ホウデン パターン サイコウチク ト ニューラルネットワーク ニ ヨル ヘンデンショ ノ ゼツエン シンダン

この論文をさがす

抄録

<p>Several studies for partial discharge (PD) pattern recognition using artificial neural network (ANN) were reported in the early 1990s. Usually, in an actual field such as a substation, data on partial discharge is scarcely available, or even rare. In many cases, the power supply phase required for the PRPD pattern cannot be easily obtained. We propose an ANN method that shifts the phase in which the maximum signal intensity detected with PD sensors is generated and used it as training and input data, even for the few phases resolved PD data available in the field. This ANN method was applied to the PRPD pattern obtained in a practical field. As a result, it was shown that the discrimination rate between PD and noise was improved, and therefore the proposed ANN method was found to be effective.</p>

収録刊行物

参考文献 (10)*注記

もっと見る

詳細情報 詳細情報について

問題の指摘

ページトップへ