A Short-Circuit Protection System Considering the Negative Sequence of Fault Current Available to Long Distribution Lines
-
- Hirayama Koki
- Nagoya Institute of Technology
-
- Aoki Mutsumi
- Nagoya Institute of Technology
-
- Amau Toru
- Chubu Electric Power Grid Co. Inc.
-
- Otani Tetsuo
- Central Research Institute of Electric Power Industry
-
- Ozawa Tatsuya
- Meiryo Denshi
-
- Tsushima Kosuke
- Meiryo Denshi
Bibliographic Information
- Other Title
-
- 事故電流の逆相分を用いた長距離配電線対応短絡保護システム
Description
<p>A fault current measured at a distribution substation is small in case of a two-phase short-circuit fault near the end of a long distribution line. This characteristic makes it difficult to settle the overcurrent relay installed at the root of line because the load current could hardly be distinguished from the fault current. On the other hand, a negative-sequence current relay likely isolates such a two-phase short-circuit fault, but it may not operate properly due to effects of load on the distribution line. This study sets a proposal of short-circuit protection system considering the negative sequence of fault current that can be applied to long distribution lines. It also demonstrates how useful the proposed system is for isolating such a two-phase short-circuit fault on a long distribution line.</p>
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 143 (6), 389-395, 2023-06-01
The Institute of Electrical Engineers of Japan