Abstract

<p>The paper proposes a method to select a power factor for an inverter of distributed power generation systems to keep appropriate voltage of a power system with the high penetration of inverter-interfaced generation. The increase of inverter-interfaced power sources, such as wind and photovoltaic power generation, arouses concerns on the voltage fluctuations in a power system. While constant power factor control of an inverter has been studied as a means to stabilize the voltage of a power system, there still remains room to improve the control. The proposed method in the paper selects the power factor based on the R/X ratio of the looking-back impedance into the interconnected power system. By normalizing the related variables, a general formula is derived for the power factor; and the resultant relationship between the apparent power and voltage of an inverter becomes identical irrespective of the R/X ratio with the control. Sample studies show that, by operating an inverter with the power factor, voltage fluctuations are effectively suppressed even for a power system with the high penetration of inverter-interfaced generation.</p>