Study of Optimal Operation for an HVAC System

DOI

Bibliographic Information

Other Title
  • 熱源・空調システムの最適制御技術の導入に向けた研究
  • 第1報−冷却水温度の設定値最適化と実測による効果検証
  • Part 1-Optimization of Cooling Water Temperature Set Point, and Verification of Energy-Saving Effects by Actual Measurement

Abstract

<p>Since it is now possible to obtain detailed data for HVAC systems, it has become increasingly clear that there has been wastage during the operation of HVAC systems, which so far went unnoticed, and that there is room for further energy-saving. The aim of this study is to develop an optimal operation technology for HVAC systems. In order to achieve this, HVAC systems must operate according to the outside air conditions and load conditions to eliminate wasteful operation. A heat source system was modeled using an energy simulation tool, and the energy consumption of the system was calculated. The outside air conditions, load conditions, and cooling water temperature set point (outlet of cooling tower) were discretized for a case study. The influence of change in cooling water temperature set point on the energy consumption of the system was examined. By analyzing the trend, a relational formula for the optimal set point of cooling water temperature was derived. Using the relational formula, an optimal control method was applied to an actual heat source system. By introducing this method, the energy consumption of the system could be reduced by 3.3%. The effectiveness of the method was confirmed by a demonstration experiment.</p>

Journal

Details 詳細情報について

  • CRID
    1390564238038432768
  • NII Article ID
    130007504938
  • DOI
    10.18948/shase.42.248_11
  • ISSN
    24240486
    0385275X
  • Text Lang
    ja
  • Data Source
    • JaLC
    • CiNii Articles
  • Abstract License Flag
    Disallowed

Report a problem

Back to top