A Study for Grounding Method of a Voltage Source Converter Type Back-to-Back System

  • Nakamura Fuminori
    Transmission & Distribution Systems Center, Mitsubishi Electric Corporation
  • Tahata Kazuyori
    Transmission & Distribution Systems Center, Mitsubishi Electric Corporation
  • Onishi Ryota
    Transmission & Distribution Systems Center, Mitsubishi Electric Corporation
  • Ise Toshifumi
    Nara-Gakuen Incorporated Educationl Institution

Bibliographic Information

Other Title
  • 自励式BTBシステムの接地方式検討
  • ジレイシキ BTB システム ノ セッチ ホウシキ ケントウ

Search this article

Abstract

<p>The grounding of a Back-to-Back system is necessary in order to determine the valve insulation level. The commonly used method is direct grounding of the negative side of the DC voltage but this method requires the full of the DC voltage. The authors proposed a neutral point grounding method with a reactor. The authors studied the required value of the reactor. Then the authors studied the miniaturization method of the reactor.</p>

Journal

References(4)*help

See more

Details 詳細情報について

Report a problem

Back to top