- Nakamoto Tetsuya
- Toshiba Energy Systems & Solutions Company
Bibliographic Information
- Other Title
-
- 三相非対称電流遮断時の過渡回復電圧
- サンソウ ヒタイショウ デンリュウ シャダンジ ノ カト カイフク デンアツ
Search this article
Description
<p>Using the current injection method, how to calculate the transient recovery voltages in three-phase asymmetrical current interruption in analysis has been devised. This calculation is applicable to both effectively earthed neutral system and non-effectively earthed neutral system. Since the transient recovery voltages of three-phase test duty T100a are calculated, the performance of the circuit breaker in three-phase asymmetrical current interruption can be estimated more correctly in synthetic testing.</p>
Journal
-
- IEEJ Transactions on Power and Energy
-
IEEJ Transactions on Power and Energy 140 (12), 851-857, 2020-12-01
The Institute of Electrical Engineers of Japan