Prediction of Heat Transfer Performance of Air-cooled Condensers Using Alternative Refrigerants R123 and R134a instead of R11 and R12
-
- Fujii Tetsu
- Institute of Advanced Material Study, Kyushu University
-
- Kogawa Hidehiko
- Institute of Advanced Material Study, Kyushu University
Bibliographic Information
- Other Title
-
- 代替冷媒R123およびR134aを用いた空冷凝縮器の伝熱性能の予測
- ダイタイ レイバイ R123 オヨビ R134a オ モチイタ クウレイ ギョ
Search this article
Abstract
When refrigerants R11 and R12 are replaced by respective alternatives R123 and R134a in air-cooled condensers for invariable values of the heat exchange rate, inlet vapor temperature, logarithmic mean temperature difference, air-side equivalent heat transfer coefficient and inner tube diameter, the change of heat transfer area is predicted to be plus 5% for R123 and minus 2% for R134a, while that of mass flow rate to be plus 6~7% for R123 and minus 15~20% for R134a.
Journal
-
- 九州大学機能物質科学研究所報告
-
九州大学機能物質科学研究所報告 7 (2), 191-193, 1994-03-31
Institute of Advanced Material Study Kyushu University