Evaluation of Grid-Forming Inverters' Impact on Transient Stability and Proposal of Effective Inverter Placement in Power System and Operation Method

Bibliographic Information

Other Title
  • Grid-Formingインバータによる過渡安定性の向上効果解析と効果的な配置構成の立案手法検討

Abstract

<p>Due to penetration of generators connected to power grid via Grid-Following inverters, transient stability of power system is deteriorated. In contrast, Grid-Forming inverters can provide virtual inertia and synchronizing power, and are expected to contribute to system stability. In this paper, the influence of GFM location in the power system and control parameters on transient stability is evaluated by RMS simulation. Then based on aforementioned analysis result, method to determine optimal location and control of GFM is proposed and verified using EAST10 model.</p>

Journal

References(11)*help

See more

Details 詳細情報について

Report a problem