Stability Evaluation of R 1132(E) Mixed Refrigerants

Bibliographic Information

Other Title
  • R 1132(E)混合冷媒の安定性評価
  • -Investigation of Self-decomposition of R 1132(E) and Energy Source in Compressor-
  • -R 1132(E)の自己分解反応と圧縮機内のエネルギー源調査-

Search this article

Description

<p>R 1132(E), an HFO refrigerant with extremely low GWP and high efficiency, is known to occur self-decomposition reaction by external energy source. In this study, we evaluated the conditions for occurrence of self-decomposition and the discharge energy in compressor for using of R 1132(E) mixed refrigerants. It was found that self-decomposition was less likely to occur as the R 1132(E) concentration decreased, and refrigerants containing R 1132(E) at < 35mass% was stable for excessive discharge energies. The quantification of the discharge energy showed that the energy in 2.2kW compressor was less than 1J. From these results, the composition ratio of R 1132(E) mixed refrigerants which can be used stably as refrigerant were clarified. .It was clarified that these results indicated clarifying the conditions for stable use of R 1132(E) mixed refrigerant.</p>

Journal

Details 詳細情報について

  • CRID
    1390583934056985216
  • DOI
    10.11322/tjsrae.24-30lg
  • ISSN
    2185789X
    13444905
  • Text Lang
    ja
  • Data Source
    • JaLC
  • Abstract License Flag
    Disallowed

Report a problem

Back to top