Detection of OPGW Water Immersion Faults by 1.24/1.625 µm Optical Transmission Loss Measurement

  • Morimura Shun
    System Engineering Research Labs., Central Research Institute of Electric Power Industry

Bibliographic Information

Other Title
  • 1.24/1.625 µm光伝送損失測定によるOPGW浸水障害検出
  • 1.24/1.625mm ヒカリデンソウ ソンシツ ソクテイ ニ ヨル OPGW シンスイ ショウガイ ケンシュツ

Search this article

Description

<p>OPGW (OPtical fiber composite overhead Ground Wire), which is used as communication lines for electric power companies, freezes and causes communication faults in winter season because of rainwater immersion into aluminum pipe (OP unit) which envelops optical fibers. Thus, effective detection methods of water immersion are needed. Hydrogen gas is generated when corrosion reaction of water and aluminum occurs, and causes optical transmission loss in wavelengths of 1.24/1.625 µm. This article argues about a water immersion detection method using 1.24/1.625 µm-OTDR (Optical Time Domain Reflectometer) and some experiments demonstrating increasing of hydrogen gas volume and optical transmission loss in real OP units.</p>