複層金属ダクトの性能に関する研究 (第2報)結露限界実験及び実建物への検討

DOI

書誌事項

タイトル別名
  • Study on Performance of Double Layer Metal Duct (Part2) Experiment of Dew Condensation Limit and Examination for Actual Building

抄録

<p>In this report, the results of experiments on the dew condensation limit of the double layer metal duct. Due to the air leak, the location where dew condensation occurs was different. In addition, the dew point temperature of the flange was lower than that of the duct surface. For the evaluation when introduce the actual building, the diagram of dew condensation limit created from the thermal network was used. As a result, dew condensation did not occur on the duct surface.</p>