書誌事項
- タイトル別名
-
- Effect of Precision of Voltage Harmonics and Ground Capacitance on the Accuracy of Ground Fault Detection
この論文をさがす
説明
<p>Recently, with the rapid increase in electric power supply, ground faults such as electric shocks and fires frequently occur. Hence, leakage protection has become increasingly important. Meanwhile, with the development of power electronic technology, distortions in power systems owing to power supply switching have increased considerably. In this paper, we present the leakage current caused by ground capacitance when the system voltage includes harmonics, and a large error is noted in the measurement results of the ground fault detection method Ior, which is currently mainstream.</p>
収録刊行物
-
- 電気学会論文誌D(産業応用部門誌)
-
電気学会論文誌D(産業応用部門誌) 142 (12), 935-940, 2022-12-01
一般社団法人 電気学会
- Tweet
キーワード
詳細情報 詳細情報について
-
- CRID
- 1390857226429027200
-
- ISSN
- 13488163
- 09136339
-
- 本文言語コード
- ja
-
- データソース種別
-
- JaLC
- Crossref
- OpenAIRE
-
- 抄録ライセンスフラグ
- 使用不可