3505 Study of Ferroresonance Phenomena in the BT Feeding Circuit
-
- Hamagishi Hirokazu
- West Japan Railway Co.
-
- Kawasaki Hiroki
- West Japan Railway Co.
-
- Matsui Yasunori
- West Japan Railway Co.
-
- Tomita Katsuya
- West Japan Railway Co.
-
- Sugiura Hajime
- West Japan Railway Co.
-
- Tsuji Youji
- West Japan Railway Co.
-
- Tanaka Hiroki
- West Japan Railway Co.
-
- Yamanoi Takashi
- West Japan Railway Co.
-
- Kawahara Keiji
- West Japan Railway Co.
Bibliographic Information
- Other Title
-
- 3505 BTき電回路における鉄共振現象の解明
Search this article
Description
In the BT feeding circuit of double track, residual voltage is sometimes generated in one track when the circuit breaker of the other side is opened. This phenomenon occurs only when one track loses power, and it disappears when the other track with power loses. This phenomenon was found to be Ferroresonance Phenomena. In the normal BT feeding circuit of double track, feeding voltage is about 22 kVrms (60 Hz), and voltage of about 3 kVrms (60 Hz) in track without power is induced by the other track with power. When Ferroresonance Phenomena occur, voltage of about 9 kVrms (20 Hz) is generated. We succeeded in suppressing it by connecting the resistor to the secondary side of ST (Signal Transformer). This paper explains the method.
Journal
-
- Jointed railway technology symposium
-
Jointed railway technology symposium 2015 (22), "3505-1"-"3505-4", 2015-12-08
The Japan Society of Mechanical Engineers
- Tweet
Keywords
Details 詳細情報について
-
- CRID
- 1570572702524528128
-
- NII Article ID
- 110010046797
-
- NII Book ID
- AA11902503
-
- Text Lang
- ja
-
- Data Source
-
- CiNii Articles