An Investigation on the Individual Measurement of Earth Resistance in a mutually Bonded Earth Electrode System

Bibliographic Information

Other Title
  • 連接接地系における接地抵抗の個別測定に関する検討

Search this article

Description

In NTT's telecommunication buildings, it has been difficult to measure the earth resistance of a telecommunication system's grounding after services have started because the grounding conductor cannot be removed from the earth electrode. Recently, earth electrodes of most of the buildings have been mutually bonded to protect the facilities against lightning surges, to it has become difficult to measure the earth resistance of the individual earth electrodes. Futhermore, the measurement itself has become difficult using the traditional earth tester, which uses assistant electrodes, since the land around most telecommunication buildings has been paved with asphalt or concrete. We have developed a new method of measuring the earth resistance of each of the mutually bonded electrodes under these circumstances.

Journal

References(4)*help

See more

Details 詳細情報について

  • CRID
    1571980077313852416
  • NII Article ID
    110003185687
  • NII Book ID
    AA11135980
  • Text Lang
    ja
  • Data Source
    • CiNii Articles

Report a problem

Back to top