Experiment of Time Synchronizing Equipment in SDH network

Bibliographic Information

Other Title
  • SDH装置を用いた時刻同期装置の試作と特性

Search this article

Description

We experimentally manufactured four links of time synchronizing devices which transmit time signals in DDC in an SDH network to examine their accuracies.Without removing noises, synchronism error was experimentally to be about ±0.36μs on four links.Even if delay variations due to transmissiosn equipment and media are added, an accruracy of the order of microseconds will be obtained.It means that these devices are applicable to new concepts of powersystem protection and control systems.By removing noises of transmission lines and time synchronous devices, time synchronism accuracy would be improved according to noise analysis.

Journal

Citations (3)*help

See more

References(4)*help

See more

Details 詳細情報について

  • CRID
    1572261552260491776
  • NII Article ID
    110003195851
  • NII Book ID
    AN10013072
  • Text Lang
    ja
  • Data Source
    • CiNii Articles

Report a problem

Back to top