Measurement of Transient State of Polarization in Actual OPGW by Lightning

Bibliographic Information

Other Title
  • 雷撃によるOPGW伝搬光の偏波変動の実測

Search this article

Description

This paper describes a field measurement of optical polarization characteristics in actual OPGW (Optical fiber composite Ground Wire) of Hokuriku electric company in the condition of lightning. As a result, transient fluctuations of polarization are detected 51 times in two half months. These waves feature the rise time 0.05-0.2msec and damping oscillation of 2-5kHz in 2-5msec. The maximum shift on Poincare sphere is 165 degree. By estimating the locations of lightning with LLS(Lightning Location System) data and power line trip records, the transients of polarization are caused by lightning attacks distant from observed OPGW within 60km.

Journal

  • Technical report of IEICE. OCS

    Technical report of IEICE. OCS 95 (343), 45-52, 1995-10-27

    The Institute of Electronics, Information and Communication Engineers

Citations (1)*help

See more

References(9)*help

See more

Details 詳細情報について

  • CRID
    1572261552314765312
  • NII Article ID
    110003285638
  • NII Book ID
    AN10060797
  • Text Lang
    ja
  • Data Source
    • CiNii Articles

Report a problem

Back to top