Measurement of Transient State of Polarization in Actual OPGW by Lightning
-
- KURONO Masahiro
- Central Research Institute of Electric Power Industry
-
- ISAWA Kiyoyuki
- Tohoku Electric Power Co., Inc.
-
- KURIBARA Masayuki
- Central Research Institute of Electric Power Industry
Bibliographic Information
- Other Title
-
- 雷撃によるOPGW伝搬光の偏波変動の実測
Search this article
Description
This paper describes a field measurement of optical polarization characteristics in actual OPGW (Optical fiber composite Ground Wire) of Hokuriku electric company in the condition of lightning. As a result, transient fluctuations of polarization are detected 51 times in two half months. These waves feature the rise time 0.05-0.2msec and damping oscillation of 2-5kHz in 2-5msec. The maximum shift on Poincare sphere is 165 degree. By estimating the locations of lightning with LLS(Lightning Location System) data and power line trip records, the transients of polarization are caused by lightning attacks distant from observed OPGW within 60km.
Journal
-
- Technical report of IEICE. OCS
-
Technical report of IEICE. OCS 95 (343), 45-52, 1995-10-27